Eight Zone Conventional Add On

The Eight Zone Conventional Board has been designed for the LoopSense range of fire alarm control panels, providing the ability to interface to conventional zones

FEATURES

  • Allows LoopSense to support conventional detectors
  • Ability to accommodate for up to 40 detectors per zone
  • The board supports up to eight conventional zones, LoopSense can support up to four boards, resultantly providing for up to 32 conventional zones
  • Supports Apollo Orbis, Series 60, Series 65, Hochiki, Nittan Sensortec and the Argus Aurora ranges of conventional detectors
  • Features a programmable end of line (EOL) that allows for 3K3, 4K7, 6K8 and 10K resistor values or 10uF capacitor for use with head removal diode bases
  • Maximum alarm current per zone is 25 mAs
  • The zone interface circuitry is capable of recognising and reporting the following conditions:
    1. Normal
    2. Open Circuit
    3. Short Circuit
    4. Alarm
  • Can be programmed to function in the following modes:
    1. Normal (latching)
    2. Non-latching/Self Reset
    3. Dependency A, B and C (EN54-2 and AS7240-2)
    4. Alarm Investigation facility
 