Eight Zone Conventional Board
The Eight Zone Conventional Board has been designed for the LoopSense range of fire alarm control panels, providing the ability to interface to conventional zones
FEATURES
- Allows LoopSense to support conventional detectors
- Ability to accommodate for up to 40 detectors per zone
- The board supports up to eight conventional zones, LoopSense can support up to four boards, resultantly providing for up to 32 conventional zones
- Supports Apollo Orbis, Series 60, Series 65, Hochiki, Nittan Sensortec and the Argus Aurora ranges of conventional detectors
- Features a programmable end of line (EOL) that allows for 3K3, 4K7, 6K8 and 10K resistor values or 10uF capacitor for use with head removal diode bases
- Maximum alarm current per zone is 25 mAs
- The zone interface circuitry is capable of recognising and reporting the following conditions:
- Normal
- Open Circuit
- Short Circuit
- Alarm
- Can be programmed to function in the following modes:
- Normal (latching)
- Non-latching/Self Reset
- Dependency A, B and C (EN54-2 and AS7240-2)
- Alarm Investigation facility